Full Description
These requirements apply to materials for the fabrication of air duct and air connector systems for use in accordance with the Standards of the National FireProtection Association for the Installation of Air-Conditioning and Ventilating Systems, NFPA No. 90A, and the Installation of Warm Air Heating andAir-Conditioning Systems, NFPA No. 90B.
The air ducts and air connectors covered by these requirements include preformed lengths of flexible or rigid ducts, materials in the form of boards for fieldfabrication of lengths of rigid ducts, and preformed flexible air connectors.
For the purpose of these requirements, air ducts and air connectors are classified as follows:
Class 0 ? Air ducts and air connectors having surface burning characteristics of zero.
Class 1 ? Air ducts and air connectors having a flame-spread index of not over 25 without evidence of continued progressive combustion and a smoke-developedindex of not over 50.
A product that contains features, characteristics, components, materials, or systems new or different from those in use when the Standard was developed, and thatinvolves a risk of fire, electric shock, or injury to persons, shall be evaluated using the appropriate additional component and end-product requirements as determinednecessary to mai ntain the level of safety for the user of the product as originally anticipated by the intent of this Standard.